5 Minimum Arc Flash Label Requirements from NFPA 70E 2018
There is no legally enforced standard for arc flash labels (also called arc flash stickers), so many different examples exists.
The NFPA 70E standard by the National Fire Protection Association in the USA is generally used.
However, it is not enforced by the OSH Act of 1970 in the USA. It is considered a Consensus Standard.
In most countries, it is used as a guideline only.
So, what should be on the label?
This article describes the minimum label requirements as specified in NFPA 70E.
Note that NFPA 70E specify exceptions so that you can customise your labels, or use no labels at all! If you have the necessary controls in place.
This article includes arc flash label examples, based on NFPA 70E requirements.
I have also includes my recommendations at the end.
NFPA 70E specifies two types of labels. They are based on the two official Arc Flash Study Methods in NFPA 70E.
-
The Incident Energy Method:
The Incident Energy and arc Flash Boundary are calculated with a set of equations.
-
The PPE Category Method:
The PPE Category and Arc Flash Boundary are selected from pre-defined tables.
The exact text for the arc flash label requirements from NFPA 70E is shown below.
- Nominal system voltage
- Arc flash boundary
- At least one of the following:
- Available incident energy and the corresponding working distance, or the arc flash PPE category in Table 130.7(C)(15)(a) or Table 130.7(C)(15)(b) for the equipment, but not both
- Minimum arc rating of clothing
- Site-specific level of PPE
There are basically 5 minimum requirements for the arc flash label.
1. Arc Flash WARNING or DANGER Sign
A clear WARNING or DANGER sign must be displayed on the label.
In the USA, a WARNING or DANGER sign is used according to ANSI Z535, "Series of Standards for Safety Signs and Tags". The choice between a WARNING and DANGER sign is not clear. The guidelines from ANZI Z535 are in the table.
Most sites in the USA use a WARNING sign.
| DANGER | A hazard which, if not avoided, will result in death or serious injury. |
| WARNING | A hazard which, if not avoided, could result in death or serious injury. |
In Australia, a DANGER sign is typically used, according to AS 1319-1994, "Safety signs for the occupational environment". The choice between a WARNING and DANGER sign is also not clear. The guidelines from AS 1319 are shown below.
Most sites in Australia use a DANGER sign.
| DANGER | A hazard which, if not avoided, will result in death or serious injury. |
| WARNING | A hazard which, if not avoided, could result in serious injury. |
The difference between the USA and Australia is in the description of a WARNING sign. In Australia, the WARNING contains only "serious injury". In the USA it contains "death or serious injury".
2. Arc Flash Hazard Description
This is just a short text that describes the hazard. In can be Arc Flash Hazard. Or just Arc Flash.
3. Nominal Voltage
The nominal voltage of the equipment. For example, 480 VAC, 600 VAC, 15,000 VAC, 15 kV, etc.
4. Arc Flash Boundary
The Arc Flash Boundary is the distance at which the incident energy equals 1.2 cal/cm2. At 1.2 cal/cm2, an operator is likely to receive second-degree burns if arc-rated PPE is not used.
With the Incident Energy Method, the Arc Flash Boundary is calculated with a set of equations.
With the PPE Category Method, the Arc Flash Boundary is selected from predefined tables in NFPA 70E.
5. Minimum PPE requirements
One of the following must be on the label:- 5A: Incident Energy at the working distance in cal/cm2
- 5B: Minimum PPE Rating in cal/cm2
- 5C: PPE Category from 1 to 4.
You are allowed to have both 5A Incident Energy (5A) and Minimum PPE Rating (5B) on the label.
You are not allowed to have PPE Category (5C) with Incident Energy (5A) or 5B Minimum PPE Rating (5B) on the label.
NFPA 70E also have an option for Site-Specific PPE Requirements. Many sites use a variation of 5C. See My Personal Arc Flash Label Recommendation.
5A. Incident Energy at the working distance in cal/cm2
The calculated incident energy in cal/cm2 at the specified working distance. This is only applicable when the Incident Energy Method is used. It is calculated with a set of equations specified in IEEE 1584.5B. Minimum PPE rating in cal/cm2
The Minimum PPE rating in cal/cm2. This is only applicable when the Incident Energy Method is used. There are no specific requirements in NFPA. However, Table 130.5(G) in NFPA specifies the following two ranges for when the incident energy method is used.- Between 1.2 cal/cm2 and 12 cal/cm2.
- Greater than 12 cal/cm2.
More specific PPE requirements are covered in NFPA 70E.
5C. PPE Category
The Arc Flash PPE Category from Table 130.7(C)(15)(c) in NFPA 70 must be shown on the label. This is only applicable when the Incident Energy Method is used.
As mentioned, only the Arc Flash PPE Category from Table 130.7(C)(15)(c) in NFPA 70 must be used when the Arc Flash PPE Category method is used. You are not allowed to display the Incident Energy as well.
However, it is confusing because you are allowed to use your Site-Specific PPE requirements. And a lot of sites define their own PPE Categories, which are based on the NFPA categories anyway. See My Personal Arc Flash Label Recommendation for an example.
These sites typically calculate the energy with the Incident Energy Method and then select the relevant PPE Category based on the cal/cm2 value. If you do this, I suggest you display only the PPE Category on the label.
The 4 Arc Flash PPE Categories from NFPA are summarised below. The detailed PPE clothing requirements are specified in NFPA 70E.
| Category | Minimum arc rating of PPE |
|---|---|
| 1 | 4 cal/cm2 |
| 2 | 8 cal/cm2 |
| 3 | 25 cal/cm2 |
| 4 | 40 cal/cm2 |
Arc Flash Label Examples showing the Minimum NFPA 70E Requirements
Arc Flash Label Example for the USA and Australia is shown for the Incident Energy Method and the PPE Category Method.
USA
Incident Energy Method
PPE Category Method
Australia
Incident Energy Method
PPE Category Method
My Arc Flash Label Recommendation
This is my recommendation. It is applicable to large industrial sites. Yes, you may completely disagree with me. And that is fine. Because, as mentioned, there are many correct ways.
However, I would really appreciate it if you could email me your comments.
1. WARNING or DANGER Label
Use a WARNING label in the USA and a DANGER label in Australia.2. Hazard Description
Use "Arc Flash Hazard" or "Arc Flash".3. System Voltage
Show the Nominal System Voltage.4. Standardized Arc Flash Boundaries
I suggest you standardize the Arc Flash Boundaries, based on worst-case scenarios. You can use the pre-defined Arc Flash Boundaries in NFPA 70E Table 130.7(C)(15)(a) or Table 130.7(C)(15)(b). They are specified for the PPE Category Method. Or you can define your own, based on your own calculations. For example:
| Cat | Voltage | Arc Flash Boundary |
|---|---|---|
| 2 | 400-1000 VAC | 20 ft (6 m) |
| 4 | 400-1000 VAC | 40 ft (12 m) |
| 4 | 1kV to 15kV | 40 ft (12 m) |
I find it confusing when the Incident Energy Method is used, and every label has a different Arc Flash Boundary. I prefer to use only one or two worse-case values everywhere. It is easy to remember.
Note that, at the Arc Flash Boundary, you will theoretically still receive first-degree burns. Not second-degree burns though. So there is no harm in extending short distances to standardize.
5. Site-specific PPE Category
I suggest you define 2 Site-Specific PPE Categories, based on NFPA 70E Table 130.7(C)(15)(c). See the example below.
This will allow you to define exactly what PPE is required per category. NFPA 70E provides options that may be confusing to interpret.
You can use either the incident Energy Method or the PPE Category Method to determine the required PPE. However, it is best to use one method for consistency. If you use the PPE Category method, you find that some of your equipment does not fit into the PPE Category tables, with respect to fault level and clearing time. In these cases, NFPA 70E suggests that you use the Incident Energy Method.
Whichever method you choose, I recommend that you display only the Site-Specific PPE Category on the label.
I believe this approach is simple, clear and less ambiguous.
| Cat. | Rating | PPE |
|---|---|---|
| 2 | 8 cal/cm2 |
|
| 4 | 40 cal/cm2 |
|