Generator full load current calculator
The generator current calculator calculates the full load current of a single-phase and 3-phase generator.
See Also
- Cable sizing calculator AS/NZS3008
- Maximum demand calculator AS/NZS3000
- Arc Flash Calculator IEEE 1584
Parameters
- Rated voltage (Vp): The rated voltage of the generator in volt (V).
- Phase: Specify the phase arrangement. 1 Phase AC or 3 phase AC.
- Generator rating (S): Specify the generator rating in kW or kVA. When the rating is in kW, you also need to specify the power factor cos(Φ), which is a number between 0 and 1. You can use approximately 0.80 if the load consists of motors only. For purely resistive loads the power factor cos(Φ) is 1.
How to calculate the full load current of a 3-phase generator?
The full load current for a 3-phase generator specified in kW is calculated as:
\(I=\displaystyle\frac{1000 \cdot S_{kW}} {\sqrt{3} \cdot V_{LL} \cdot \cos{\phi} }\)
Where,- Skw is the generator rating in kilowatts (kW).
- VLL is the generator line-to-line rated voltage in volt (V).
- cos(Φ) is the power factor.
\(I=\displaystyle\frac{1000 \cdot 50} {\sqrt{3} \cdot 480 \cdot 0.85} \)
I = 70.8 A.
The full load current for a 3-phase generator specified in kVA is calculated as:
\(I=\displaystyle\frac{1000 \cdot S_{kVA}} {\sqrt{3} \cdot V_{LL} }\)
Where,- Sva is the generator rating in kilo-volt-ampere (kVA).
- VLL is the generator line-to-line rated voltage in volt (V).
\(I=\displaystyle\frac{1000 \cdot 50} {\sqrt{3} \cdot 480 }\).
I = 60.1 A.
How to calculate the full load current of a single-phase generator?
The full load current for a 1-phase generator specified in kW is calculated as:
\(I=\displaystyle\frac{1000 \cdot S_{kW}} { \cdot V_{LN} \cdot \cos{\phi} }\)
Where,- Skw is the generator rating in kilowatts (kW).
- VLN is the generator line-to-neutral rated voltage in volt (V).
- cos(Φ) is the power factor.
\(I=\displaystyle\frac{1000 \cdot 5} { 120 \cdot 0.85} \)
I = 19.6 A.
The full load current for a 3-phase generator specified in kVA is calculated as:
\(I=\displaystyle\frac{1000 \cdot S_{kVA}} { \cdot V_{LN} }\)
Where,- Skw is the generator rating in kilo-volt-ampere (kVA).
- VLN is the generator line-to-neutral voltage in volt (V).
\(I=\displaystyle\frac{1000 \cdot 50} { \cdot 480 }\).
I = 16.7 A.
Frequently asked questions
How to calculate the full load current of a generator?
For a three-phase generator, the full load current is calculated as I = 1,000 × S / (√3 × V). Where, S is the generator rating in kilo-volt-ampere (kVA), and V is the generator rated voltage in volt (V). For a single-phase generator, the full load current is calculated as: I = 1,000 × S / V.
How many amps is a 3,000 watt generator?
If it is a 3,000 watt (3 kW), single-phase, 120 V generator, and the allowable load power factor is 0.8, then the current will be: I = 3,000 / (120 × 0.8) = 31.25 A.
How many amps is a 10,000 watt generator?
If it is a 10,000 watt (10 kW), 3-phase, 120 V generator, and the allowable load power factor is 0.8, the current will be: I = 10,000 / (√3 × 120 × 0.8) = 60.1 A. If it is a 3-phase- 240 V generator, the current will be: I = 10,000 / (√3 × 240 × 0.8) = 30.1 A.
How many amps is a 7,500 watt generator?
If it is a 7,500 watt (7.5 kW), single-phase 120 V generator, and the allowable load power factor is 0.8, the current will be: I = 7,500 / (120 × 0.8) = 78.1 A.